Recent Projects - Hotels
92 Room Hotel - Windsor Mill, MD
This newly constructed 5 story, 92 room hotel in the city of
Windsor Mill, MD had inadequate water pressure from the city. It
is critical to have very good water pressure in any hotel, to
properly operate the high volume shower heads and other
fixtures.

Towle Whitney supplied an overunder duplex variable speed
booster system with a small footprint for installation in a tight
mechanical room. The pumps operate in a lead/lag sequence
and the lead pump alternates every 48 hours supplying constant
high pressure to all rooms while achieving significant energy
savings.

Model #        TW2000U-140R-40 Overunder Duplex
Pump HP      3.4HP each
Volume         140 GPM total
Boost            40 PSI
Towle Whitney designs and builds variable speed booster pump systems for hotels of all sizes. Some of our recent projects are listed
below. A small description of each project specifies the parameters of plumbing setup, the  basis for booster system design and the
information regarding the system that was installed:
101 Room Hotel - Monahans, TX
Another newly constructed 4 story, 101 room hotel in the city of
Monahans, TX had inadequate water pressure from the city and
the top floor rooms had very low pressure.

Towle Whitney supplied an modular duplex variable speed
booster system with a compact footprint and modular design for
ease of transportation and assembly. The system was built for a
100% redundancy plus lead/lag and alternation to exercise both
pumps equally.

Model #        TW2000U-150R-40 Duplex
Pump HP      3.4HP each
Volume         150 GPM total
Boost            40 PSI
106 Room Hotel - Bar Harbor, ME
The water pressure supplied by the city was inadequate for the
top two floors of this 106 room 4 story hotel in Bar Harbor, ME. A
high TDH [total dynamic head] was needed to bring the water
pressure on these floors to 60 PSI.

Towle Whitney designed a customized duplex booster system
with each of its pumps capable of supplying 60 PSI boost over
existing pressure. The suction & discharge manifolds were
capped with interchangeable roll grooved couplings to facilitate
access from either side.


Model #        TW2000S-120W-60 Duplex
Pump HP      3HP each
Volume         120 GPM total
Boost            60 PSI
21 Londonderry Turnpike, Hooksett, NH 03106        www.towle-whitney.com        PH: 800-807-9827        Fax: 603-626-7372        info@towle-whitney.com
©2014 Towle Whitney LLC